| LOAD CELL SYSTEM FAULT FINDING
GUIDE
1. Basic Checks
This first chapter is intended to aid in fault
finding in load cell systems using Wheatstone bridge type load cells.
The items covered are designed to assist in checking connection
of the load cell and obtaining a display from a load cell monitor.
Since only a load cell and monitor are being checked the main purpose
is to isolate whether any problems seen arise from the load cell
or the monitor. For other load cell system requirements such as
alarm setting and retransmission outputs consult the instruction
manual of the load cell monitor being used.
Equipment required: A multimeter capable of
measuring Ohms, Volts and mV. To test the monitor independently
a load cell simulator will be required.
1.1 Basic load cell system
The basic load cell system consists of a 4
wire load cell connected to a load cell monitor. The monitor supplies
a voltage called the excitation voltage to the load cell and the
load cell returns a millivolt (mV) signal back to the monitor. The
mV signal changes with the load experienced by the load cell and
this mV signal is used to determine the display value on the monitor.

1.2 Basic load cell resistance checks
Unfortunately there is no standard wiring
colour code for load cells so you will need to know from data supplied
with the cell which wires are the excitation wires and which wires
are the signal wires (see section 2.6 for colour code examples).
If you do not have this information then as shown in the diagram
above in addition to the 4 resistance elements which make up the
Wheatstone bridge there are commonly one or two resistors in the
excitation lines. This means that the resistance across the excitation
wires is usually the highest resistance measured across any two
wires. The resistances also vary between manufacturers and load
cell types, input and output resistance values are often provided
in the data supplied with the load cell.
To test the cell obtain a meter
capable of measuring Ohms, measure across each pair of wires in
turn and record the results (space provided in the table which follows).
The load cell must be completely disconnected from the monitor and
at no load when these tests are made.
The table which follows gives measurements
taken with a sample 350 Ω load cell with one resistor in its
Ex+ line i.e. these readings show lowest values between signal lines
and Ex-. For a load cell with two resistors in its excitation lines
(one in Ex+ and one in Ex-) you would expect the Ex+ and Ex- to
S+ and S- measured values to be roughly the same. In a typical load
cell the S+ to S- should be close to the specified output resistance
of the cell i.e. within one or two Ohms, other values are nominal.
| Resistance
check |
Typical
350 Ω |
Record
your readings |
Record
your readings |
Record
your readings |
|
Ex+ to Ex - 410
Ω approx |
- |
- |
- |
- |
|
S+ to S- 350 Ω
approx |
- |
- |
- |
- |
|
Ex + to S+ 315
Ω approx |
- |
- |
- |
- |
|
Ex+ to S- 315
Ω approx |
- |
- |
- |
- |
|
Ex- to S+ 280
Ω approx |
- |
- |
- |
- |
|
Ex- to S- 280
Ω approx |
- |
- |
- |
- |
If the resistance readings appear to be correct
move on to section 1.3. If the resistance readings appear to be
incorrect e.g. outside expected range, open circuit or short circuit
across any two wires then the likely cause is a damaged or faulty
load cell or incorrect/faulty wiring.
1.3 Checks when load cell is connected to
monitor
When installing a load cell system the usual
installation procedure would be:
- Install load cell in position
- Connect excitation and signal wires to
monitor
- Calibrate monitor to read the load in
the units required e.g. kg or Tonnes (consult monitor instruction
manual for calibration procedures
- Check monitor is reading correctly over
a range of values
If you wish to check the system prior to installation
or if the load cell will not calibrate or the monitor can not be
made to read correctly or is giving unstable readings make the following
measurements.
- Using a voltmeter measure and record the
excitation voltage
- Using a mV meter measure and record the
signal voltage at the lowest load you can apply
- Using a mV meter measure and record the
signal voltage at a load as close to the rating of the load cell
as possible
- Obtain the mV/V output figure from the
load cell data supplied with the load cell and compare the signal
changes seen with the theoretical values from the load cell data.
1.4 Other common system problems
Some common problems which may cause difficulty
when installing a system:
- Incorrect wiring of load cell to monitor
- i.e. signal & excitation wires crossed at one or more points.
In AIC monitors this is likely to show an error message of ----
or -or - on the display.
- Friction or restriction of load cell movement
- If the load cell is prevented from moving freely due to friction
or is prevented from moving to its full deflection due to an obstacle
the output from the load cell will not be correct. Typical display
reading indications are that the display is slow to respond to
load changes and/or that the display does not always return to
zero when expected and/or that the display is not linear. Check
that there are no obstructions to free movement and that the load
cell is mounted correctly.
- Over stressed load cell - If the load cell
becomes over stressed sufficiently it will take on a permanent
deformation. This will lead to a high offset voltage which may
make it impossible to calibrate successfully and may also lead
to non linearity over its operating range.
- Moisture in the load cell or wiring - if
moisture is allowed to enter the electrical circuit of the load
cell or wiring the display reading will change due to current
flowing through both the load cell bridge and the new current
paths created by moisture. Ensure that cells of the correct environmental
protection (IP) rating are used for the application and that moisture
cannot enter the cable through cuts, cable joins and exposed cables.
- High resistance cable joins - When a load
cell cable is extended it is important that the joins made are
electrically sound and free from moisture. A damp or corroded
join will lead to unreliable readings.
- Incorrect mounting of the load cell - Load
cells are manufactured in many types e.g. shear beam, "S"
type etc. Each type requires a particular form of mounting for
correct operation. Check the load cell type and mounting requirements
if in doubt.
- Electrical damage to load cells - Electrical
damage can often occur due to lightning strikes, welding on the
structure to which the load cell is attached and other causes.
Surge suppression devices for load cell systems are available
from suppliers such as MTL. Welding currents will destroy the
cell. If welding on the structure is likely and the load cell
is not insulated from the current flow, copper or stainless steel
braids should be used to connect each end of the load cells to
ground to help prevent electrical damage.
- Non linearity of display reading - Friction
& restriction as described in 2. above could be the cause
of non linearity. With some load cell designs, particularly those
designed for high loads e.g. Tonnes the output of the cell may
be non linear over parts of its measurement range, typically the
low load end of the curve may not be quite linear. Some load cell
monitors allow extra calibration points to correct this non linear
output from the cell. It is also worth checking in instruments
with this feature that the linearising functions have been turned
off if they are not required i.e. if it is turned on and the cell
output is linear the linearising functions may make it appear
non linear.
1.5 Technical assistance
To save time when seeking assistance, as much
as possible of the information below should be obtained before contacting
the monitor or load cell manufacturer for technical assistance.
Photocopy this page and fill in as much information as you can.
| Question |
Record
your answer |
|
Model number of
monitor |
- |
|
Model number of
load cell |
- |
|
Capacity of load
cell |
- |
|
mV/V output of
load cell |
mV/V |
|
Load cell resistance |
Ex+ to Ex- Ω |
|
Load cell resistance |
S+ to S- Ω |
|
Load cell resistance |
Ex+ to S+ Ω |
|
Load cell resistance |
Ex+ to S- Ω |
|
Load cell resistance |
Ex- to S+ Ω |
|
Load cell resistance |
Ex- to S- Ω |
|
Excitation voltage measured |
V |
|
mV signal at low load &
load value |
mV at load |
|
mV signal at high load &
load value |
mV at load |
|
Monitor mV/V input range setting |
mV/V |
APPENDIX
2.1 mV/V explained
When a load cell is obtained it is usually
accompanied by a certificate which details the specifications for
the load cell including the signal output span per volt of excitation
or mV/V output.
Usually the output from a load cell will be
approximately 0mV at zero load though typically there may be a small
offset voltage at zero load. Over the full rated capacity of the
load cell the mV output will change. The amount by which it changes
depends on the resistance change in the cell and on the excitation
voltage applied. Since the load cell manufacturer does not know
what excitation voltage will be applied to the cell rather than
quote the mV output overfull range they will quote the millivolt
output per volt of excitation or in its short form mV/V.
For example a 250kg load cell may be quoted
as having a 2.357mV/V output. If the excitation voltage is 1 0V
they you could expect a mV output of 0mV at zero load and 23.57mV
at 250kg load. Again the actual voltages seen could be affected
by a usually small offset voltage.
2.2 Load cell types

 |
Shear beam - the shear
beam load cell is fixed rigidly at one end with the force being
applied to the other end. These can be used singly or in groups
e.g. a platform scale using one cell in each corner. |
 |
Double ended shear beam
type cells are of different construction and are fixed rigidly
at each end with the force being applied to the centre of the
beam. |
 |
Single point load cells
are of similar design. |
 |
Compression
- the compression load cell is designed to operate in compression
only. Some designs require load to be applied at one end only,
other designs can be compressed by force at both ends. |
 |
S type
- the S type load cell can be used in tension and compression.
The signal voltage output will reverse in polarity when the
force changes from tension to compression i.e. the display value
may change from.
Tension load cells and Load links are designed to operate under
tension only. |
 |
Rope clamp
- the rope clamp load cell is popular in hoist and crane
applications due to it ease of installation. The rope passes
through the cell and when tension is applied to the rope due
to a weight being lifted the tension produces a bending force
on the cell.
The mounting position of this type of load cell is very important.
Most of these type of cells are mounted at the dead end of the
rope allowing enough rope at each end for flexing i.e. ensure
that the attachment is not so close to the dead end that the
rope is rigid and cannot flex.
Since these cells are designed to operate over a very wide range
of loads and rope sizes, and because the rope system often goes
through a series of ''drops'', it is often the case that the
mV output from these cells is at the low end of the range. The
sensitivity of the monitor may need to be increased by lowering
the mV range to compensate. |
|
Load pin
- load pin cells are designed to be installed in the axis of
a sheave, shackle etc. through which force is applied. Most
common load pins will measure force in one direction only. The
direction of force is often marked with an arrow at one end
of the pin or instructions for alignment may be given in the
load cell certificate. If the load is off axis, the output will
be reduced. At 90 degrees off axis the output will not change
with a change in load. |
2.3 Six wire load cells
Six wire load cells use two extra wires known
as sense or reference wires. These sense wires connect to the excitation
wires at the load cell as shown below. Monitors which will accept
6 wire load cells measure the current passing down the Ex+ to SEN+
and Ex- to SEN- wires. This measurement allows the monitor to compensate
for any resistance changes in the wiring to the load cell due to
changes in temperature.
As can be seen below the sense wiring can
be tested using an Ohm meter. The resistance between
Ex+ & SEN+ and Ex- & SEN- should be no more than a few Ohms.

2.4 Single & multi-point weighing
Single point weighing
- single point type load cells can be used with single load cell
platform designs, usually in fairly low capacity systems. S type,
tension type, rope clamp & load pins load cells are also used
in single point systems.
Two point weighing
- can be used for longer thin platforms, beams and girders e.g.
load cell near each end.
Three point weighing
- often used in weighing vertical cylinders. Using 3 points gives
less complicated leveling than when more load cells are used.
Four point weighing
-typically used with high capacity platform scales and rectangular
containers
More than 4 points
-typically used in very high capacity and/or very large container/platform
measurement systems
Using pivots and load cells - savings
in load cell costs are often made by using pivots e.g. instead of
using two load cells the load on a beam can be measured by using
a load cell at one end and a pivot on the other. The use of a pivot
is not recommended unless accuracy is not important. If a pivot
is used instead of an extra cell it must be taken into account that
the mechanical design must allow adequate and linear transference
of load to the load cells in the system. Any friction in the pivot
will result in slow response, inaccurate and non repeatable measurements
|